| How is the
primary air flow measured?
The only way to accurately measure the primary air flow
is by reading the static pressure in the primary air plenum. A
test opening provided in the unit for this purpose. When this
pressure is plotted on the primary air flow V’s plenum static
pressure chart provided with each project, the air flow can be
read. Do not take readings in the duct near the unit and presume
it will be the same in the plenum. It could be up to 100Pa out,
or more.
Are inspections i.a.w. AS3666 necessary,
and if so, at what frequency?
Yes, but only if the system creates condensate on the secondary
coil. In this case, not usual for office building installations,
the inspections would be the same as for any air handler with
a condensing cooling coil. For the dry coil operation, the unit
and drip tray should be inspected once a year for any foreign
matter that might have found its way there.
How frequently do you need to clean lint
screens?
Very infrequently. It is recommended that in the first year of
operation, an inspection be made after three months operation.
If clean, make it six months to the next inspection. Based on
recent installations, yearly inspections should be adequate. Refer
also to Item 'Comparing Systems'
earlier in these FAQ’s.
Can the capacity of a terminal unit be
altered after installation?
No. At least, not easily if the intention is a change to the design
total capacity of the unit. The load varies in normal operation
by varying the secondary water flow. The primary air pressure
and number of nozzles set the primary air quantity, a constant
flow, with variations in air temperature to the outdoor air temperature
schedule.
If the unit had small nozzles, these might be changed to the medium
nozzles to increase the primary air figure. This should be referred
to the Dadanco technical staff. There may have been additional
holes provided for nozzles that were plugged at time of manufacture.
This is not the normal case. If it were so, the plugs could be
replaced with nozzles. This assumes the primary air system can
supply the additional air.
The units are not intended for field alteration and any proposal
to do so should be referred to Dadanco.
Can the handing of the secondary coil be
changed in the field?
Yes. While the unit will be supplied with the coil orientation
agreed prior to manufacture, the coil can be changed in the field.
The coil is retained with brackets, which can be removed, the
coil rotated and the brackets replaced. There will also be changes
to the connecting piping – but it can be done.
Will condensation occur if I have bad or
poorly maintained controls?
It could. You should have them fixed! With the quality controls
you have installed, the sensors will have detected the change
in secondary water temperature and/or the high room dew point
and will have initiated the pre-arranged controls program to raise
an alarm with the maintainer; to reset the secondary water temperature
upwards. As a last resort, the program will stop the secondary
water pump until the fault is corrected.
|